상세설명
| Digital Inputs | |
| Digital Type | DC Input(Sink/Source) |
| Number of channels | 16 channels |
| On Voltage | 10 VDC min.(30 VDC max.) |
| Off Voltage | 5 VDC max. |
| off current | 1 mA. max. (at 5-VDC) |
| Input current | 6 mA max.(at 24-VDC) |
| Number of circuits percommon | 16 points/common |
| On delay | 1 ms max. |
| Off delay | 1 ms max. |
| I/O power supply voltage | ±24 VDC nominal, ±30 VDC max. (±48 VDC optional) |
| Isolation method | Photocoupler isolation |
| Isolation voltage | 3,750 Vrms |
| Digital Outputs | |
| Digital Type | Signal Relay Output(SPST NO) |
| Number of channels | 8 channels |
| Internal I/O common | MOSFET P-Channel |
| Rated load | Resistance load 125 VAC 0.3 A/output, common 8 A 30 VDC 2 A/output, common 8 A |
| Number of circuits percommon | 8 points/common*8 |
| Maximum contact voltage | 125 VAC, 110 VDC |
| Maximum contact current | 2 A/output |
| Maximum switchingcapacity | 37.5 VAAC, 60 WDC |
| Minimum applicable load (reference value) | 10mVDC10uA |
| Mechanical service life | 50,000,000 operations min. |
| Electrical service life | 50,000 operations min. (2A 30 VDC, resistive load) 100,000 operations min. (1A 30 VDC, resistive load) |
| Operate time | 4ms max. |
| Release time | 4ms max. |
| I/O power supply method | The relay drive power is supplied from the module powersupply. |
| Modulet power supply currentconsumption | 100 mA max. (at 24-VDC) |
| Isolation method | Relay isolation |
| Isolation voltage | 1,500 Vrms(Between contact and coil) |
| Digital Inputs | |
| Digital Type | Dry Contact Input / Wet Contact Input |
| Number of channels | 16 channels |
| On Voltage | Switch On(Internal 5 VDC) / 3 VDC min.(30 VDC max.) |
| Off Voltage | Switch Off / 1.5 VDC max. |
| off current | 1 mA. Max. (at 5-VDC) |
| Input current | 8 mA max.(at 24-VDC) / 6 mA max.(at Switch On) |
| Number of circuits percommon | 16 points/common |
| On delay | 1 ms max. |
| Off delay | 1 ms max. |
| Input filter value | Without filter, 0.5 ms, 1 ms, 2 ms, 4 ms, 8 ms, 16 ms, 32 ms (Default setting: 1 ms) |
| I/O power supply voltage | Internal 5 VDC / +5 to +24 VDC,+30 VDC max. |
| Isolation method | Photocoupler isolation |
| Isolation voltage | 3,000Vdc |
| Digital Outputs | |
| Digital Type | Signal Relay Output |
| Number of channels | 8 channels(SPST NO) |
| Rated load | Resistance load 125 VAC 0.3 A/output, common 8 A 30 VDC 2 A/output, common 8 A |
| Number of circuits percommon | 8 points/common*8 |
| Maximum contact voltage | 125 VAC, 110 VDC |
| Maximum contact current | 2 A/output |
| Maximum switchingcapacity | 37.5 VAAC, 60 WDC |
| Minimum applicable load (reference value) | 10mVDC10uA |
| Mechanical service life | 50,000,000 operations min. |
| Electrical service life | 50,000 operations min. (2A 30 VDC, resistive load) 100,000 operations min. (1A 30 VDC, resistive load) |
| Operate time | 4ms max. |
| Release time | 4ms max. |
| I/O power supply method | The relay drive power is supplied from the module powersupply. |
| Modulet power supply currentconsumption | 100 mA max. (at 24-VDC) |
| Isolation method | Relay isolation |
| Isolation voltage | 1,500 Vrms(Between contact and coil) |