Digital Outputs | |
Digital Type | AC/DCRelay Output(SPST NO) |
Number of channels | 8, 16 channels |
Rated load | Resistance load 250 VAC 5 A/output, common 8 A 30 VDC 5 A/output, common 8 A |
Number of circuits percommon | 8 points/common |
Maximum contact voltage | 250 VAC, 125 VDC |
Maximum contact current | 5 A/output |
Maximum switchingcapacity | 1,250 VAAC, 150 WDC |
Minimum applicable load(reference value) | 5 VDC 1mA |
Mechanical service life | 20,000,000 operations min. |
Electrical service life | 1,000,000 operations min. (3 A 250 VAC, 30 VDC, resistive load) 50,000 operations min. (5 A 250 VAC, 30 VDC, resistive load) |
Operate time | 10ms max. |
Release time | 5ms max. |
I/O power supply method | The relay drive power is supplied from the module powersupply |
Modulet power supply currentconsumption | 150 mA max. (at 24-VDC) |
Isolation method | Relay isolation |
Isolation voltage | 3,000 Vrms(Between contact and coil) |
Digital Outputs | |
Digital Type | Signal RelayOutput |
Number of channels | 8, 16 channels(SPST NO) |
Rated load | Resistance load 125 VAC 0.3 A/output, common 8 A 30 VDC 2 A/output, common 8 A |
Number of circuits percommon | 8 points/common*8 |
Maximum contact voltage | 125 VAC, 110 VDC |
Maximum contact current | 2 A/output |
Maximum switchingcapacity | 37.5 VAAC, 60 WDC |
Minimum applicable load(reference value) | 10mVDC10uA |
Mechanical service life | 50,000,000 operations min. |
Electrical service life | 50,000 operations min. (2A 30 VDC, resistive load) 100,000 operations min. (1A 30 VDC, resistive load) |
Operate time | 4ms max. |
Release time | 4ms max. |
I/O power supply method | The relay drive power is supplied from the module powersupply. |
Modulet power supply currentconsumption | 100 mA max. (at 24-VDC) |
Isolation method | Relay isolation |
Isolation voltage | 1,500 Vrms(Between contact and coil) |
Digital Outputs | |
Digital Type | Signal RelayOutput |
Number of channels | 6, 12 channels(SPDT NO, NC) |
Rated load | Resistance load 125 VAC 0.3 A/output, common 8 A 30 VDC 2 A/output, common 8 A |
Number of circuits percommon | 6 points/common*6 |
Maximum contact voltage | 125 VAC, 110 VDC |
Maximum contact current | 2 A/output |
Maximum switchingcapacity | 37.5 VAAC, 60 WDC |
Minimum applicable load(reference value) | 10mVDC10uA |
Mechanical service life | 50,000,000 operations min. |
Electrical service life | 50,000 operations min. (2A 30 VDC, resistive load) 100,000 operations min. (1A 30 VDC, resistive load) |
Operate time | 4ms max. |
Release time | 4ms max. |
I/O power supply method | The relay drive power is supplied from the module powersupply. |
Modulet power supply currentconsumption | 100 mA max. (at 24-VDC) |
Isolation method | Relay isolation |