상세설명
| Digital Outputs | |
| Digital Type | AC/DCRelay Output(SPST NO) |
| Number of channels | 8, 16 channels |
| Rated load | Resistance load 250 VAC 5 A/output, common 8 A 30 VDC 5 A/output, common 8 A |
| Number of circuits percommon | 8 points/common |
| Maximum contact voltage | 250 VAC, 125 VDC |
| Maximum contact current | 5 A/output |
| Maximum switchingcapacity | 1,250 VAAC, 150 WDC |
| Minimum applicable load(reference value) | 5 VDC 1mA |
| Mechanical service life | 20,000,000 operations min. |
| Electrical service life | 1,000,000 operations min. (3 A 250 VAC, 30 VDC, resistive load) 50,000 operations min. (5 A 250 VAC, 30 VDC, resistive load) |
| Operate time | 10ms max. |
| Release time | 5ms max. |
| I/O power supply method | The relay drive power is supplied from the module powersupply |
| Modulet power supply currentconsumption | 150 mA max. (at 24-VDC) |
| Isolation method | Relay isolation |
| Isolation voltage | 3,000 Vrms(Between contact and coil) |
| Digital Outputs | |
| Digital Type | Signal RelayOutput |
| Number of channels | 8, 16 channels(SPST NO) |
| Rated load | Resistance load 125 VAC 0.3 A/output, common 8 A 30 VDC 2 A/output, common 8 A |
| Number of circuits percommon | 8 points/common*8 |
| Maximum contact voltage | 125 VAC, 110 VDC |
| Maximum contact current | 2 A/output |
| Maximum switchingcapacity | 37.5 VAAC, 60 WDC |
| Minimum applicable load(reference value) | 10mVDC10uA |
| Mechanical service life | 50,000,000 operations min. |
| Electrical service life | 50,000 operations min. (2A 30 VDC, resistive load) 100,000 operations min. (1A 30 VDC, resistive load) |
| Operate time | 4ms max. |
| Release time | 4ms max. |
| I/O power supply method | The relay drive power is supplied from the module powersupply. |
| Modulet power supply currentconsumption | 100 mA max. (at 24-VDC) |
| Isolation method | Relay isolation |
| Isolation voltage | 1,500 Vrms(Between contact and coil) |
| Digital Outputs | |
| Digital Type | Signal RelayOutput |
| Number of channels | 6, 12 channels(SPDT NO, NC) |
| Rated load | Resistance load 125 VAC 0.3 A/output, common 8 A 30 VDC 2 A/output, common 8 A |
| Number of circuits percommon | 6 points/common*6 |
| Maximum contact voltage | 125 VAC, 110 VDC |
| Maximum contact current | 2 A/output |
| Maximum switchingcapacity | 37.5 VAAC, 60 WDC |
| Minimum applicable load(reference value) | 10mVDC10uA |
| Mechanical service life | 50,000,000 operations min. |
| Electrical service life | 50,000 operations min. (2A 30 VDC, resistive load) 100,000 operations min. (1A 30 VDC, resistive load) |
| Operate time | 4ms max. |
| Release time | 4ms max. |
| I/O power supply method | The relay drive power is supplied from the module powersupply. |
| Modulet power supply currentconsumption | 100 mA max. (at 24-VDC) |
| Isolation method | Relay isolation |
| Isolation voltage | 1,500 Vrms(Between contact and coil) |