상세설명
| SPECIFICATIONS | |
|---|---|
| Measuring function | AC leakage current and AC load current |
| Display | LCD max.3200 count with annunciators |
| Range | AC 3000mA/30A/300A/3000A(50Hz/60Hz) |
| Range selector | 4 range manual by rotary switch |
| Measuring sensor | Flexible current sensor |
| Inside diameter of sensor | φ210mm |
| A/D Conversion | Dual slope integration method |
| Filter function | By filter switch (Low pass filter:150Hz) |
| Over range indication | "OL" mark on LCD |
| Data hold indication | "DH" mark on LCD |
| Low battery indication | "Battery" mark on LCD |
| Auto power off | Approx. 10 minutes after power on (Auto power off function can be released by the connection of recorder) |
| Sampling rate | 2 time/sec. |
| Analog signal output | DC 300mV full scale to each range(±2%F.S.) (Output impedance: less than 10kΩ) |
| Withstanding Voltage | AC 2200V/1 minute between flexible sensor and outer case |
| Limitation of circuit voltage | Less than AC 600V |
| Operating Temperature | 0~45℃, < 80%RH (without condensation) |
| Storage Temperature | -10~60℃, < 70%RH (without condensation) |
| Power supply | LR6, AM-3 or AA size battery×6 |
| Size | Main unit:159(W)×105(H)×53(D)mm Flexible current sensor:Approx.650mm length with 2m lead |
| Accessories | Carrying case, Batteries, Instruction manual |
| Option | Cable for recorder |